|
This 5,000 squarefoot timber frame Net Zero residence located on
Martha’s Vineyard is powered by a 10 kW wind turbine. Annually,
the wind turbine output is greater than the power used by the house
and the geothermal system.
The project location on a hill made a horizontal geothermal installation
impossible. The solution was to install a six ton vertical direct
exchange geothermal system inside the basement mechanical room
using a compact drill rig. Direct exchange geothermal was chosen
due to the extremely difficult drilling conditions; each of the
six loops is only 100’ long.
A six ton refrigerant to water heat pump provides hot and chilled
water to fan coils and radiant floors via buffer tanks. DHW preheat
is provided by the heat pump with final heat provided by an electric
water heater. Tekmar controls provide three separate mix temperatures
for the six radiant zones. A direct digital control system is
used to coordinate the system and provide dew point control and
mixing - in the future, fan coils will be used for dehumidification
using water below the room dewpoint; then the fan coil return
water will be mixed with the water in the radiant floors to provide
sensible radiant cooling.
Net Zero Residence, Longview -
project details
One of the primary goals of the mechanical system at the Longview
Residence was sustainability – we had to ensure that our
annual power use of the mechanical system (combined with the power
use of the whole house) would be met and/or exceeded by the on-site
wind turbine. While first cost was important, long term energy
efficiency and reliability was paramount. The very low maintenance
requirements of a geothermal system and low energy use made this
installation attractive to the homeowner.
Numerous features help to make this system green and more energy
efficient: Because the homeowner did not want to see outside condensing
units, wanted an all electric mechanical system, and wanted high
efficiency with low maintenance, we proposed the use of a geothermal
heat pump. A horizontal field was impossible due the shape of
the site so a vertical (actually diagonal) installation was approved.
To minimize drilling costs and borehole depths we chose to use
a direct exchange refrigerant based system.
After a careful cost/benefit analysis of comparing building shell
improvements (to the insulation and windows) with the reduction
in mechanical equipment size (and consequent lifetime energy savings),
the geothermal installation was sized at six 100’ diagonal
boreholes.
Drilling was exceedingly difficult due to the geology of the
site – the drill crew encountered twenty feet of sand, then
enormous 20’ boulders left over from the glacier that formed
Martha’s Vineyard at the end of the last Ice Age, then layers
of sand, then more boulders. Needless to say, the pounding the
drill rig endured was tremendous. Fortunately, the direct exchange
borehole diameter was only 4” instead of 6” or 8”
as is common with closed loop glycol systems.
The effort was worth it as the entire manifold system for the
vertical borehole field is directly under the mechanical room
floor with little chance for damage from future landscaping or
construction projects.
Timber frame made the installation of ductwork difficult so radiant
space heating (and future space cooling) and three fan coils for
heating, cooling, and dehumidification were installed in various
zones throughout the residence.
Plastic water heaters were chosen to greatly reduce long term
maintenance as the water quality was fairly aggressive. Their
2” foam insulation also greatly reduced standby loss
which allowed for more efficient loading of the geothermal heat
pump.
The direct digital control (DDC) system allowed us to optimize
system operation and reduce the size and cost of the mechanical
plant.
The DDC evaluates outside temperature, dominant mode of operation
(heating or cooling), current chilled water and hot water buffer
tank temperatures, and the current setpoint (based on heating
and cooling outset temperature schemes) to determine how best
to use the output of the heat pump.
During the shoulder seasons where cooling and heating may be
required, the DDC controls heat pump output to cool the chilled
water buffer tank and heat the hot water buffer tank through a
diverting valve. Domestic hot water preheat is giving priority
and the heat pump, via a second diverting valve, heats up the
preheat tank through a flat plate heat exchanger.
By decoupling the distribution system (fan coils and their respective
circulators and the radiant floors and their circulators) from
the generation/storage system (the heat pump and its buffer tanks),
this system can maximize the full load (and hence most efficient)
run time of the heat pump.
By using the DDC to control heating, cooling, and DHW preheat
functions, one heat pump can perform the three tasks, thereby
reducing equipment size and cost.
As the shoulder seasons change into winter or summer, the DDC
switches priority of hot or chilled water operation based on outside
temp and dominant mode of heating or cooling.
Each fan coil unit has two sets of coils, one that receives chilled
water and is equipped with a condensation pan and the other that
uses hot water for heating. The DDC will allow us to heat a space
with radiant floor heating and dehumidify with the chilled water
coil and then reheat with the hot water coil – a scenario
that often occurs in the shoulder seasons due the proximity to
the ocean.
During the coldest parts of winter, the DDC can also change the
chilled buffer tank into a second hot buffer tank and both coils
in the fan coil can be used for heating. As the heat load is dominant
in our locale, this strategy allows us to shrink the size of the
fan coils and their subsequent equipment and energy cost.
The DDC system is capable of providing dew point control for
radiant cooling – the fan coils will be used for dehumidification
using water below the room dewpoint (generated using a cooling
reset temperature scheme in the chilled water buffer tank). The
return water from the fan coils will be mixed as necessary with
the water in the radiant floors to provide sensible radiant cooling
at temperatures above the room dewpoint.
|